Hydro-Optic UV System performs automated dose control, UVT monitoring and water stream disinfection.
RZB300-12 is an enhanced system of the RZB300-11 Hydro-Optic UV System. With four high intensity medium pressure UV lamps and total internal reflection from the walls of the quartz reactor, the system provides high level disinfection. MPHI lamps provide broad-spectrum water stream disinfection exposing bacteria, viruses and protozoa to the germicidal wavelengths of the UV light. The first sensor is installed in front of the lamp to evaluate lamp intensity. The second sensor is mounted some distance away from the lamp and measures water clarity. Total Internal Reflection (TIR) recycles the UV light energy in the Hydro-Optic UV chamber providing longer UV light paths. The customized control provides user-friendly integration with plant controls, remote monitoring and customized user setting for alarm values. The optional Deposit Prevention Mechanism (DPM) keeps quartz tubes deposit-free.
Atlantium RZB300-12 Hydro-Optic System includes:
- Disinfection unit
- Ballast module
- Controller
Operating conditions
The maximum operating water stream temperature is 60 °C (140 °F). The maximum maintenance water temperature is 90 °C (194 °F). The maximum ambient temperature is 40 °C (113 °F). The maximum working pressure is 7 bar (102 PSI).
Brand | Atlantium Technologies |
Number of lamps | 4 |
Max Power Consumption (lamp only) | 16.8 kW |
Length of lamp (mm/inch) | 417.8 / 16.4 |
Unit Length (mm/inch) | 1209 / 47.6 |
Unit Weight (kg/lb) | 226 / 498 |
Unit volume (liter/gallon) | 83 / 22 |
Unit chamber width at widest point (mm/inch) | 505 / 19.9 |
Required service clearance on sides (mm/inch) | 750 / 29.5 |
Minimum Height above floor (mm/inch) | 750 / 29.5 |
Standard pipe connection options | Flange DIN2576 DN350 PN16° / Flange ANSI B 16.5 14” 150lb |
Operating water temperature | 0-60°C / 32-140°F |
Maintenance water temperature | 0-90°C / 32-194°F |
Maximum ambient temperature | 40°C / 104°F |
Maximum Flow Rate | Application dependent |
Maximum working pressure | 7 bar / 102 PSI |
Disinfection chamber material | High grade fused silica (quartz) |
Housing material | Electro-polished stainless steel 316 / Super duplex |
Controller | Integrated, with flat touch screen user interface, remote monitoring and control optional |
Electricity requirements | 400VAC 3 phases / 440VAC 3 phases / 480VAC 3 phases |