Hydro-Optic UV System performs automated dose control, UVT monitoring and water stream disinfection.
RZB300-11 Hydro-Optic Water Disinfection System is developed to guarantee bio-security and reduce power consumption. Patented Hydro-Optic engineering uses fiber-optic technology. Two high intensity medium pressure UV lamps provide safe and cost-efficient water treatment. UV lamps feature excellent performance in cold and warm water. Thick quartz tubes separate UV lamps from the water chamber to eliminate the risk of water contamination. RZB300-11 automatically adjusts UV dose to changes in real-time conditions and measures actual UV dose with real-time control. Atlantium RZB300 series is a modular configuration that provides maximum flexibility and precision.
Atlantium RZB300-11 Hydro-Optic System includes:
- Disinfection unit
- Ballast module
- Controller
Operating conditions
The recommended operating water stream temperature is from 0 °C to 60 °C (32-140 °F). The required maintenance water temperature is from 0 °C to 90 °C (32-194 °F). The maximum ambient temperature is 40 °C (104 °F). The maximum working pressure is 7 bar (102 PSI).
Brand | Atlantium Technologies |
Number of lamps | 2 |
Max Power Consumption (lamp only) | 8.4 kW |
Length of lamp (mm/inch) | 417.8 / 16.4 |
Unit Length (mm/inch) | 835 / 32.9 |
Unit Weight (kg/lb) | 178 / 392.5 |
Unit volume (liter/gallon) | 69 / 18.2 |
Unit chamber width at widest point (mm/inch) | 505 / 19.9 |
Required service clearance on sides (mm/inch) | 750 / 29.5 |
Minimum Height above floor (mm/inch) | 750 / 29.5 |
Standard pipe connection options | Flange DIN2576 DN350 PN16° / Flange ANSI B 16.5 14” 150lb |
Operating water temperature | 0-60°C / 32-140°F |
Maintenance water temperature | 0-90°C / 32-194°F |
Maximum ambient temperature | 40°C / 104°F |
Maximum Flow Rate | Application dependent |
Maximum working pressure | 7 bar / 102 PSI |
Disinfection chamber material | High grade fused silica (quartz) |
Housing material | Electro-polished stainless steel 316 / Super duplex |
Controller | Integrated, with flat touch screen user interface, remote monitoring and control optional |
Electricity requirements | 400VAC 3 phases / 440VAC 3 phases / 480VAC 3 phases |