Hydro-Optic UV System performs automated dose control, UVT monitoring and water stream disinfection.
RZ300-11 Hydro-Optic Water Disinfection System is developed for real-time water stream monitoring and delivery of the required UV dose. With one high intensity medium pressure UV lamp and total internal reflection from the walls of the quartz reactor, the system provides high level disinfection. Total Internal Reflection (TIR) recycles UV light energy in the disinfection chamber. Medium pressure high intensity lamp emits a broad germicidal wavelength damaging microorganisms in the water at the DNA level and protein level, causing damage to their enzyme systems. The integrated advanced software automatically adjusts the UV power to maintain the required UV dose. HOD quartz tube separates UV lamp from the water chamber for easy and safe lamp replacement.
Atlantium RZ300-11 Hydro-Optic System includes:
- Disinfection unit
- Ballast module
- Controller
Operating conditions
The recommended operating water stream temperature is from 0°C to 60°C (32-140°F). The required maintenance water temperature is from 0 °C to 90 °C (32-194 °F). The maximum ambient temperature is 45 °C (113 °F). The maximum working pressure is 7 bar (102 PSI).
Brand | Atlantium Technologies |
Number of lamps | 1 |
Max Power Consumption (lamp only) | 4.2 kW |
Length of lamp (mm/inch) | 462.8 / 18.22 |
Unit Length (mm/inch) | 782 / 30.8 |
Unit Weight (kg/lb) | 140 / 308.6 |
Unit volume (liter/gallon) | 69 / 15.8 |
Unit chamber width at widest point (mm/inch) | 505 / 20 |
Required service clearance on sides (mm/inch) | 750 / 29.53 |
Minimum Height above floor (mm/inch) | 750 / 29.53 |
Standard pipe connection options | DIN2527 DN350 PIN16° ANSI B 14” 150lb |
Operating water temperature | 0-60°C / 32-140°F |
Maintenance water temperature | 0-90°C / 32-194°F |
Maximum ambient temperature | 45°C / 113°F |
Maximum Flow Rate | Application dependent |
Maximum working pressure | 7 bar / 102 PSI |
Disinfection chamber material | High grade fused silica (quartz) |
Housing material | Electro-polished stainless steel 316L |
Controller | Integrated, with flat touch screen user interface, remote monitoring and control optional |
Electricity requirements | 200 / 380 / 400 / 440 / 480 / 600 / VAC 3 phases 50/60 Hz |
-
Atlantium Patent Portfolio.pdfdownload